How are we going to make money?
Contribute with reserves
A balanced power system is essential to ensure a reliable electricity supply. An electricity grid must constantly be balanced between electricity production and electricity consumption to avoid excess or shortage of electricity
PCS Specifications
Item | Specification |
Full power DC Voltage Range | 623 – 1500 Vdc |
AC Output Power | 1000 kW / kVA |
Normal Grid Voltage Vrms | 400 Vac |
Normal Grid Frequency | 50Hz |
Dimensions (W x H x D) | 2200 x 2260 x 1100 mm |
Weight | 2600 kg |
Operating Temperature | -20°C to +50°C |
Relative Humidity | 0% to 95% RH, non-condensing |
Altitude | < 4000 m |
Cooling | Forced air cooling |
Safety / EMC | IEC 62477 / IEC 61000-6-2, IEC 61000-6-4 |
Grid Interconnection | VDE AR-N 4110, G99 |
IP Ratings | IPS4 |
PCS Functions
- Extremely fast response time
- 1000kW, 1200kW or 1500kW
- Up to 1500VDC
- ModBus RS482/CAN/Ethernet
- Efficiency > 95%
RACK Specifications
Item | Specification |
Cooling type | Liquid cooling |
Cell capacity (Ah) | 280 |
Dimensions (mm) | 1300 (D)*1300 (W)*2280 (H) |
Configuration | 1P*52S*8S |
Normal voltage (Vdc) | 1331.2 |
Normal energy (kWh) | 372.736 |
Weight (T) | About 3.5 |
Operating voltage (Vdc) | 1164.8~1497.6 |
BMS Certification | UL1973, GB/T 34131-2017 |
Cabinet Certification | GB/T 36276, UL1973, IEC62619, IEC 62477-1, UL9540A, IEC 61000-6-2/-4 |
Safety / EMC | IEC 62477 / IEC 61000-6-2, IEC 61000-6-4 |
Degree of protection | IP66 |